How do I encode a downlink for a water rope sensor?
NOTE: All downlinks must contain a total of (8) bytes, padded with zeros at the end when necessary. Water Rope Sensor Configuration Example: 08 02 50 00 00 00 00 00 08 Downlink Message Type ( 0x08 = Water Rope Sensor ) 02 Enable Events 0x02 Enable ...
How do I encode a Configuration Downlink for a MAXBOTIX Ultrasonic Level Sensor?
NOTE: All downlinks must contain a total of (8) bytes, padded with zeros at the end when necessary. Also note that if the configuration settings exceed the maximum ratings on the sensor, the sensor may not report an event. See User Manual ...
How do I encode a Configuration Downlink for a Tilt Sensor?
NOTE: All downlinks must contain a total of (8) bytes, padded with zeros at the end when necessary. Control Byte The table below describes the control byte bit definitions. ...
How do I encode a Configuration Downlink for a Thermocouple Temp Sensor?
NOTE: All downlinks must contain a total of (8) bytes, padded with zeros at the end when necessary. See User Manual at https://www.multitech.com/models/RB90000220LF for more information. Byte Bits Description 0 Downlink Message Type (0x13 = ...
How do I encode a Configuration Downlink for a External Probe Temp Sensor?
NOTE: All downlinks must contain a total of (8) bytes, padded with zeros at the end when necessary. See User Manual at https://www.multitech.com/brands/reveal-wireless-air-temp-humidity-sensors for more information. External Probe Temp Sensor ...
How do I encode a Configuration Downlink for a Single Push Button Sensor?
NOTE: All downlinks must contain a total of (8) bytes, padded with zeros at the end when necessary. See User Manual at https://www.multitech.com/brands/reveal-wireless-push-buttons for more information. Single Push Button Sensor Configuration ...
How do I encode a downlink for a Dry Contact Sensor?
NOTE: All downlinks must contain a total of (8) bytes, padded with zeros at the end when necessary. See User Manual at https://www.multitech.com/brands/reveal-wireless-dry-contact-sensors for more information. Configuration Example: 07 00 00 ...
How do I encode a downlink for an ABM (Acceleration Based Movement) Sensor?
NOTE: All downlinks must contain a total of (8) bytes, padded with zeros at the end when necessary. See User Manual at https://www.multitech.com/brands/reveal-wireless-movement-sensors for more information. ABM sensor Configuration Message: 0x0E ...
How do I encode a configuration downlink for a 4-20mA Current Loop Sensor?
NOTE: All downlinks must contain a total of (8) bytes, padded with zeros at the end when necessary. See User Manual at https://www.multitech.com/brands/reveal-wireless-industrial-sensors for more information. 4-20mA Current Loop Sensor Threshold ...
How do I encode a configuration downlink for a Voltage Sensor?
NOTE: All downlinks must contain a total of (8) bytes, padded with zeros at the end when necessary. For more information see the the user manual at https://www.multitech.com/brands/reveal-wireless-industrial-sensors Voltage Sensor Threshold ...
How do I encode a Configuration Downlink For Water Leak Sensor?
NOTE: All downlinks must contain a total of (8) bytes, padded with zeros at the end when necessary. Configuration Message: 0x08 Byte Description 0 Downlink Message Type (0x08 = Water Leak Sensor) 1 ...
How do I encode a Configuration Downlink for a No-Probe Temp Sensor?
NOTE: All downlinks must contain a total of (8) bytes, padded with zeros at the end when necessary. See User Manual at https://www.multitech.com/brands/reveal-wireless-air-temp-humidity-sensors for more information. No-Probe Temp ...
How do I encode a Configuration Downlink for a Door/Window Sensor?
NOTE: All downlinks must contain a total of (8) bytes, padded with zeros at the end when necessary. See User Manual at https://www.multitech.com/models/RB90000005LF for more information. Door Window Sensor Configuration Message: 0x03 Byte ...
How do I decode a Thermocouple Temperature Sensor event?
The Thermocouple Temperature Sensor will generate events based on temperature measurements rising above or falling below configured thresholds, report-on-change, and periodic messaging. Byte 0: 7-4 Byte 0: 3-0 Byte 1 Byte 2 Byte 3 and Byte 4 Byte ...
How Do I decode an Ultrasonic Level Sensor Event?
The Ultrasonic Level Sensor will generate events if the measured distance rises above or falls below the configured thresholds. Byte 0: 7-4 Byte 0: 3-0 Byte 1 Byte 2 Byte 3 and 4 Protocol version (4 bits) Counter (4 bits) Message Type Code 0x10 ...
How Do I Decode A High Precision Tilt Sensor Event?
The High Precision Tilt Sensor will generate events if when the sensor is tilted either away from or toward the vertical orientation by a specified amount. Byte 0: 7-4 Byte 0: 3-0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Protocol version (4 bits) ...
How Do I Decode a No-Probe Temperature Sensor Event
The No-Probe Temperature Sensor will generate events if the temperature rises above or falls below the configured thresholds Byte 0: 7-4 Byte 0: 3-0 Byte 1 Byte 2 Byte 3 Byte 4 Protocol version (4 bits) Counter (4 bits) No-Probe Temp ...
How do I decode a 4-20mA Current Loop Sensor Uplink Event?
The 4-20mA Current Loop Sensor will generate events if the measured value rises above or falls below the configured thresholds, rate of change, or is set for periodic reporting. Byte 0: 7-4 Byte 0: 3-0 Byte 1 Byte 2 Byte 3 and Byte 4 Protocol ...
How do I decode an External Probe Temperature Sensor Event?
The External Probe Temperature Sensor will generate events if the temperature rises above or falls below the configured thresholds. Byte 0: 7-4 Byte 0: 3-0 Byte 1 Byte 2 Byte 3 Byte 4 Protocol version (4 bits) Counter (4 bits) ...
How do I decode a Dry Contact Sensor Event?
The wireless Dry Contact Sensor detects a connection between two wires. When the wires are either shorted or opened, the Dry Contact Sensor will generate an event. Byte 0: 7-4 Byte 0: 3-0 Byte 1 Byte 2 Protocol version (4 bits) Counter ...
How do I decode a Water Rope Sensor Event?
The Water Rope Sensor will generate events when the presence of water or another liquid is detected Byte 0: 7-4 Byte 0: 3-0 Byte 1 Byte 2 Byte 3 Protocol version (4 bits) Counter (4 bits) Message Type Code (0x08) Water Rope Sensor ...
How do I decode a Voltage Sensor event?
The Voltage Sensor will generate events if the measured value rises above or falls below the configured thresholds. Byte 0: 7-4 Byte 0: 3-0 Byte 1 Byte 2 Byte 3 & 4 Protocol version (4 bits) Counter (4 bits) Message Type Code ...
How do I decode a Water Leak Sensor event?
The Water Leak Sensor will generate events when water (or another liquid) is present, and then give a value representing the relative measurement of the resistance between the probes of the sensor. The Water Leak Sensor uses that resistance to ...
How do I decode an Air Temperature and Humidity event?
The Air Temperature and Humidity Sensor will generate events when the environment changes to exceed set thresholds or on a periodic basis. Byte 0: 7-4 Byte 0: 3-0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Protocol version (4 ...
How do I decode an ABM (Acceleration Based Movement) event?
The ABM Sensor will generate events when movement is detected (that exceeds a configurable threshold). Note that this product should not be used for vibration detection. For vibration detection applications, such as detecting when a motor has turned ...
How do I decode a Door/Window Sensor event?
The Door/Window Sensor will generate events when a door (or window) is open or closed. Byte 0: 7-4 Byte 0: 3-0 Byte 1 Byte 3 Protocol version (4 bits) Counter (4 bits) Message Type Code (0x03) Event (0x01 in the example below) Protocol ...
How do I decode a Dual Push Button event?
The Dual Push Button Sensor will generate events when the either the left button, the right button, or both buttons are pressed, released, or held-down for a configurable amount of time. Byte 0: 7-4 Byte 0: 3-0 Byte 1 Byte 2 Byte 3 Protocol version ...
How do I decode a Single Push Button event?
The Single Push Button Sensor will generate events when the button is pressed, released and or held-down for a configurable amount of time. Byte 0: 7-4 Byte 0: 3-0 Byte 1 Byte 2 Byte 3 Protocol version (4 bits) Counter (4 bits) Message Type Code ...
How much does this sensor cost?
For all pricing inquires please contact sales@radiobridge.com.
My sensors join but keep rejoining
If you find that your sensors initially join but keep rejoining, set the sever to max DR3 unless you have a 64-channel gateway.
Where Can I find the AppEUI/JoinEUI?
Use the following for AppEUI/JoinEUI 01-01-01-01-01-01-01-01 Used in the following product families: RBS301, RBS304, RBS305, and RBS306 78-94-E8-00-00-00-00-00 Used in product families not listed above
Notes on using Chirpstack
Recommended General Chirpstack Configuration: (LoRaWAN Compliant): -- Make sure to use ChirpStack version >= 3.12.1 -- Set the max data rate to 3 in the Service Profile -- Set enabled_uplink_channels=[0, 1, 2, 3, 4, 5, 6, 7, 64] -- Check the "Disable ...
How do I set a temperature sensor to only report periodically?
Occasionally you may want a temperature sensor to simply report the temperature at even intervals throughout the day without specifically reporting changes or hitting thresholds. This can be achieved by setting the temperature sensor to ...
How do I know when to change the battery?
RadioBrdige Sensors are designed to provide several years of useful life before the battery needs to be changed. The effective life of the battery is dependent on many factors such as message volume, ambient temperature, signal strength and Adaptive ...
Why did my sensor come with a magnet?
Nearly all RadioBridge Sensors come packaged with a mountable magnet. For Door/Window Sensors the magnet and sensor can be mounted to the door (or window sash, enclosure lid, etc.) and frame. When the door is opened and the sensor and magnet become ...
How do I decode a Tilt event?
The Tilt Sensor will generate events when the orientation of the device transitions its vertical-horizontal axis as determined by configurable threshold angles (state transition) or when the vertical-horizontal orientation changes by a configurable ...
Can I enable a sensor to receive downlinks at any time?
A downlink message is one that is sent to the sensor from the cloud and is used to configure the sensor itself. For Class A devices, messages cannot be initiated from the cloud since the sensor is typically sleeping and the radio is turned off, so ...
Do sensors conflict when there are multiple gateways?
In general, even if more than one Gateway receives a signal from a given Sensor, the Network Server will automatically eliminate duplicate packets. Multiple Gateways should not present concerns provided the devices have been provisioned to only one ...
What kind of replacement battery should I use for RadioBridge RBS101 and RBS301 Sensors?
The RadioBridge RBS101 (SigFox) and RBS301 (LoRaWAN) Sensor families all use a single CR123 / CR123A (CR17345) Lithium Battery. Rechargeable lithium batteries are not suitable for this application. Use only non-rechargeable lithium batteries. ...
How do I set Periodic Reporting to be in hours or minutes?
Hour/Minute Periodic Reporting is only implemented in firmware 1.3 or greater. Previous versions allow intervals in hours only. Periodic Reporting is a feature available on Temperature Probe/Probeless Sensors as well as Air Temperature and Humidity ...